The meter response time is up to 5 ms.

The message transmission time can be calculated in milliseconds as follows: 10000/baud_rate * (message_length_in_bytes + 4).


For example: 

Baud Rate 19200

Message length 106 bytes


Transmission time=10000/19200*(106+4)=57.3ms